Data sheet

BG

These manual alarm Call Points have been designed for use in hazardous locations and harsh environmental conditions. The Glass Reinforced Polyester enclosures are suitable for use both onshore and offshore, where light weight combined with a high level of corrosion resistance is required.

The break glass is covered by a membrane which protects the operator from glass fragments meaning that no hammer is required to activate the unit.

A plastic ‘break glass’ or deformable operating element is available to replace the break glass. Once the flexible element is pressed it will bend but will not break. The unit is reset by repositioning the element.

  • ATEX certified.

  • IECEx certified.

  • UL listed for Haz locs.

  • UL listed for Ord locs

  • CUTR certified.

  • Chinese (CQST) certified.

  • Brazilian (Inmetro) certified.

  • Chinese Cumpulsory Certification for Fire systems (CCCF) certified.

  • IP66 and IP67.

  • Corrosion free GRP construction.

  • SIL 2 certified.

  • A variety of colours available

ATEX Ex de:

Cert. no. BAS02ATEX2105X. ATEX Approved Ex II 2G.

Certified to: EN60079-0, EN60079-1, EN60079-7.

Ex de IIC T6 Gb switch only.

Ex de mb IIC T6 Gb with LED.

Ex de mb IIC T4 Gb with resistors & diodes.

 

ATEX Ex ia:

Cert no. Baseefa 03ATEX0084X. ATEX Approved Ex II 1GD

Certified to: EN60079-0, EN60079-11.

Ex ia IIC T4 Ga, Ex ia IIIC T135ºC Da.

 

IECEx Ex ia:

Cert. no. IECEx BAS 12.0093X.

Certified to: IEC 60079-0, IEC 60079-11.

Ex ia IIC T4 Ga, Ex ia IIIC T135ºC Da.